Summary: An upright unit with two 5 hp scroll compressors (mostly Copeland), R22 refrigerant, an air-cooled condenser with four fans (two on top, two on the side) and an insulated 200-litre tank. Catalog current draw 14 A, 1-inch water connection.

Specifications (from the Alborz catalog)
| Parameter | Value |
|---|---|
| Configuration | Upright, two top fans and two side fans |
| Condenser | Air-cooled |
| Compressors | 2 × 5 hp (scroll) |
| Compressor brand | Mostly Copeland (customer may choose) |
| Evaporator | Shell-and-tube with ice bank |
| Refrigerant components | Danfoss |
| Refrigerant | R22 |
| Fans | 4, axial blower |
| Water connection | 1 inch |
| Pump | 1 hp peripheral pump |
| Tank | Insulated polyethylene, 200 L |
| Thermostat | Digital |
| Dimensions | 140 × 180 × 80 cm |
| Current draw | 14 A |
| Finish | Electrostatic powder coating |
| Wheels | Yes (portable) |
| Warranty / service | 1 year / lifetime service for all parts |
Typical applications
Two independent compressors let the chiller run on one compressor at part load, which saves power. Suited to injection molds, extruders, hydraulics and production lines with a medium heat load.
How to choose the right capacity
Real cooling capacity depends on the leaving water temperature, the ambient air temperature and the refrigerant, so it is not the same as compressor horsepower. Calculate the process heat load from Q = ṁ · cp · ΔT: for example, 10 m³/h of water with a 5 K temperature rise carries about 58 kW. Send us your operating conditions and we will size the unit for you.
Frequently asked questions
Why two compressors instead of one?
At part load only one compressor runs, so power use follows the real load, and if one compressor stops the other can keep the process cooled.
What warranty does it have?
According to our catalog: one year of warranty and lifetime after-sales service for all parts.